Environment; Symbols On The Ups And Accessories - Eaton 93E G2 100/100 User And Installation Manual

Table of Contents

Advertisement

Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
Use of the LCD control panel and the maintenance bypass switch (MBS).
Use of optional connectivity modules and their software.
Follow the precautions and only perform the described operations. Any deviation
from the instructions can be dangerous to the user or cause accidental load
loss.
Do not open any other screws in the unit than those holding the cover plates
of the MiniSlots and the MBS locking plate. Failure to recognize the electrical
hazards can prove fatal.
2.4
The UPS must be installed according to the recommendations in this document.
Never install the UPS in an airtight room, in the presence of flammable gases, or
in an environment exceeding the specifications.
Excessive amount of dust in the operating environment of the UPS may cause
damage or lead to malfunction. Always protect the UPS from the outside
weather and sunshine. In order to maximize internal battery service lifetime, the
recommended operating temperature range is from +20ºC to +25ºC.
During charge, float charge, heavy discharge, and overcharge, hydrogen and
oxygen gases are emitted from lead-acid and NiCd batteries into the
surrounding atmosphere. Explosive gas mixture may be created if the
hydrogen concentration exceeds 4% by volume in air. Ensure the necessary
air flow rate for the ventilation of the UPS location.
2.5
The following are examples of symbols used on the UPS or its accessories. The
symbols are used to alert you of important information.
©
Eaton Corporation plc 2019. All rights reserved.

Environment

Symbols on the UPS and accessories

RISK OF ELECTRIC SHOCK
Indicates that a risk of electric shock is present and the associated
warning should be observed.
CAUTION: REFER TO OPERATOR'S MANUAL
Refer to your operator's manual for additional information, such as
important operating and maintenance instructions.
DANGER
WARNING
Revision: 002
Document ID: P-164000848
User's and installation guide
13 (118)