18 Overview of assemblies

19 HMI Color Touch Screen 4,3" and 7"

A freely programmable 4.3" or 7" TFT touch display with 4
non-volatile program memories monitors and controls the
central battery system in conjunction with the ACU modu-
le. All functions such as charging, battery string monitoring,
battery block monitoring, bus phase monitor and insulation
monitoring device, mains / emergency light switchover and
deep discharge protection of the units and the connected
emergency lights are automatically tested. Occurring errors
are reported via the TFT touch display. An interface allows
the connection of a central visualization and monitoring
device.
Display Fields:
Battery voltage, battery strand charging current (+), battery
strand discharge current in test or error case (-), charging
fault, battery block temperature, battery block temperature,
phase monitor function, insulation monitor function, light
fault with destination in plain text, deep discharge protec-
tion, manual reset, emergency light running on (remaining
time in minutes), test mode, date / time, iso fault with des-
tination in plain text, failure UV-AV with destination in plain
text, error information, programming information, test log.
Function icons:
The following functions can be activated via the function
icons:
- Start duration test, abort duration test, manual reset,
- ISO troubleshooting,
- Search lights (all modules),
- Learning current values (all modules),
- log off external modules,
- Blocking, releasing,
- Simulation power failure,
- All lights on, standby light on and continuous light off
Programming Icons
Single light monitoring, circuit monitoring, individual name
(20 characters) per device, circuit, light, switch, device
address, selective manual reset, after-running emergency
light (1-15 min.), selective emergency light, LON switch,
timer function, automatic function and operating time test,
selection of menu language, password protection
Mounting- and Operating Instruction Eaton LoadStar-S JSB 40071860396 March 2021 www.ceag.de
Internal memory:
Internal memory for archiving the device configuration and
the prescribed test log information for at least 4 years.
Storage of:
• 300,000 test log entries
• Destination texts of the luminaires (40 characters per
luminaire)
• Destination texts of external switches / inputs to phase
monitors, DLS (40 digits per module)
• names of circuits (40 characters per circuit)
• Name of the installation (40 characters)
Using optional Eaton software, programming can be carried
out offline on the PC.