Cg Iv.1 Relay Module - Eaton LoadStar-S JSB Mounting And Operating Instruction

Table of Contents

Advertisement

30 CG IV.1 Relay Module

30 CG IV.1 Relay Module
The CGVI.1 relay module is suitable for snap mounting on
the LoadStar-S module subrack and enables the LoadStar-S
to be connected to a central control station (GLT). The most
important system statuses are reported via potential-free
signalling contacts. Two input channels are available for
remote checking of the LoadStar-S central battery system.
A function test can be triggered via the „FT" input channel,
and the following can be performed via the input channel
„BT" is subjected to an endurance test (battery test). Eight
LEDs indicate the system status.
Function
deep discharge protection
emergency lighting fault
charging fault
battery operation
mains operation
Switching capacity of the contacts: 24V/0,5A AC/DC
24V Function inputs
With a pulse of at least 20 ms/24 V the desired function
can be activated.
If a function or duration test is to be triggered again, the
function-duration test must be reset via a pulse.
Function test ON => 24V DC ≥ 20ms
Function test OFF => 24V DC ≥ 20ms
Battery duration test ON => 24V DC ≥ 20ms
Battery duration test OFF => 24V DC ≥ 20ms
Ordering details
type
CG IV.1
68
Mounting- and Operating Instruction Eaton LoadStar-S JSB 40071860396 March 2021 www.ceag.de
Contact
Contact
11/12
21/22
ON
-
ON
-
-
-
Description
Relay module for subrack Mounting
Contact
Contact
31/32
-
-
-
-
ON
-
-
-
-
Order No.
40071361620
Contact
41/42
51/52
-
-
-
-
-
-
ON
-
-
ON

Advertisement