Loadstar-S 20 - Eaton LoadStar-S JSB Mounting And Operating Instruction

Table of Contents

Advertisement

F

35 LoadStar-S 20

35 LoadStar-S 20
E
The LoadStar-S 20 in IP21 (IP31 optional) version with indi-
vidual cable entry in accordance with EN 50171 is suitable
for supplying up to 88 circuits for safety and escape sign
luminaires 230V / 216V AC/DC in the power range up to
17 .3KW. A configurable patch distributor for mains and
battery enables the connection of 1- phase sub-distributors
of the type LoadStar-S US 7 and LoadStar-S SOU. The
wiring system with rounded mounting panels does without
classic cable ducts and, in combination with the natural
ventilation and the large ventilation slots of the mounted
D
modules, ensures a homogeneous control cabinet climate
which has been proven by heating tests in accordance with
EN 61439-1 under nominal load conditions. The clear, self-
explanatory internal modular field structure, taking contact
protection into account, rounds off the appearance.
The extensive catalogue of cabinet accessories such as
special locks, door hinges right/left, cable glands, bases in
various heights, IP31 retrofit kits and IP54 on request offers
the right solution for most customer-specific requirements
C
without long delivery times.
The colour touch display with automatic testing device and
individual luminaire monitoring with individual status and
name indication per luminaire in conjunction with system-
related ECG / LED supply module including monitoring
module without additional data line reports and records the
operating status of the external phase monitor modules,
the insulation monitoring device as well as the battery
strings and, if battery block monitoring technology is used,
B
the operating status of each individual battery block.
A
74
Mounting- and Operating Instruction Eaton LoadStar-S JSB 40071860396 March 2021 www.ceag.de
1
2
Cable entry from above.
Roof plate with IP X1 dripping water protection foil and
holes for:
30 x M16
99 x M20
18 x M32
3 x M40
3 x M50
ATTENTION!
The dripping water protection of the film is no longer gua-
ranteed after the cables have been inserted without the
appropriate cable gland.
3
4
Erstellt/
issued
Entstanden aus/
developed from
E 100757
D
Stand/
Änderung/
index
modification
Benennung/ designation
40071362102_nV
nVent 11391-55
A
B
C
D
E
3.9.19
Kufrej
19.2.20
Kufr
3.9.19
Kufr
Datum/
Name
nam
date

Advertisement

Table of Contents
loading

Table of Contents