Circuit Change Over Module Sku.1 Cg-S 1X6A - Eaton LoadStar-S JSB Mounting And Operating Instruction

Table of Contents

Advertisement

28 Circuit change over module SKU.1 CG-S 1x6A

28 Circuit change over module SKU.1 CG-S
1x6A
The SKU.1 CG-S 1x6A circuit change over module is suita-
ble for snap mounting on the LoadStar-S module subrack,
supplies and monitors emergency lights with electronic
ballast for DC operation via a circuit feeder. CEWA GUARD
monitoring checks the function of the connected emer-
gency lights. It is possible to connect up to 20 emergency
lights. Mixed operation within a circuit of maintained light,
switched maintaineds light and non-maintained light is
possible with STAR technology. An additional data line is
not required for SKU.1 type CG-S.
The individual switching of the emergency lighting circuits
enables separate fusing of the battery and mains supply
of the emergency lighting so that in the event of a simple
earth fault and failure of the mains fuse, the battery can
continue to be supplied via the IT grid. The high rated
power in combination with an inrush short-circuit current
of up to 250A enables the supply of emergency luminaires
with high power consumption and high short-circuit cur-
rents. The arrangement of the circuit fuses on the front
of the module makes it easy to replace them in the event
of a short circuit or overload. The LED on the front of the
unit automatically reports total faults which are indicated in
detail on the HMI. Thus one receives very comfortably all
necessary information.
Technical description
Inputs
Rated voltage AC
Rated voltage DC
Rated frequency
Outputs Rated current
Short-circuit current
Switching cycles
cos phi kapazitiv
Maximum own consumption
Ambient temperature
Degree of protection
Protection class
Number of circuits
Rated current per circuit
Fuse protection per circuit
Max. inrush peak current
Max. wire cross-section
Dimensions and weight
H x W X D (in mm)
Module width
Typical switching over time:
Ordering details
type
SKU.1 CG-S 1 x 6A
66
Mounting- and Operating Instruction Eaton LoadStar-S JSB 40071860396 March 2021 www.ceag.de
220-240 V
184-275 V
50 or 60 Hz
6A
1500 A
10000
0,5 - 1,0
4W
-5°C...+55°C
IP20
2
1
6A
10AT
250 A
2.5 mm2
0.49 kg
170 x 55 x 155
1 TE (1 and 55 mm)
AC auf DC = 450 ms
Description
Circuit switching 1 x 6A for Snap subrack Mounting 40071361570
In addition, the generously designed ventilation slots ensu-
re optimum air circulation and heat transport. An automatic
insulation fault search in combination with the BCM.1
module and the colour touch screen makes the initial com-
missioning considerably easier.
Current value monitoring is possible, but should only be
used in exceptional cases where individual monitoring is
not possible for technical reasons. It must be ensured that
the failure of a single light is detected which is difficult with
lights with low power consumption such as LED lights due
to the supply voltage and ambient temperature fluctuations
of the light. It is not possible to precisely locate individual
defective luminaires.
Order No.

Advertisement

Table of Contents
loading

Table of Contents