37 Connection distributor Battery
The battery power supply of the LoadStar-S 20 is provided
by a modular battery connection distributor. The distributor
contains a size 00C switch-disconnector with a maximum
connection cross-section of 50 mm2 and enables the con-
nection of up to 6 substations to modular size D02-E18 bat-
tery outgoing distributors and the associated terminals for
the earth conductors. The components are simply plugged
on from the front and securely contacted.
Name:
Assembly:
Degree of protection:
Protection class:
Rated voltage (Battery):
Rated current (Battery):
Maximum number of outgoing distributors
modules
Module
Terminals Connection cross-sections
Mains feed:
Terminals Connection cross-sections
Mains Distribuiton:
Ordering details
type
Outgoing distribution module Battery
for busbar mounting
Busbar cover profile
Mounting- and Operating Instruction Eaton LoadStar-S JSB 40071860396 March 2021 www.ceag.de
Data:
On busbar
IP20
I
216 V DC
IN =63 A
6
50 mm² Rigid/flexible
16 mm² Rigid/flexible
50 mm² Rigid/flexible
Description
Incl. 2 pieces screw caps E18 and 3 pieces D02-
fuse links 25A
Cover profile in module width for clip mounting to
the bottom tray profile
37 Connection distributor Battery
Pos.
Order No.
40071347161
40071347192
77