Electrical Installation
Enclosure
Power (hp [kW])
A1
0.37–1.5
A2
0.37–4.0
A3
7.5–10 [5.5–7.5]
A4
0.5–4 [0.37–4]
A5
0.5–10 [0.37–7.5]
B1
15–20 [11–15]
B2
25–30 [18.5–22]
B3
15–20 [11–15]
B4
25–40 [18.5–30]
C1
40–60 [30–45]
C2
75–100 [55–75]
C3
40–60 [37–45]
C4
75–100 [55–75]
Table 9.4 380–500 V, Enclosure Types A, B and C
MG33BF22
Design Guide
Recommended
Recommended
fuse size
max. fuse
gG-10
gG-10 (0.37–3)
gG-16 (4)
gG-16
gG-10 (0.37–3)
gG-16 (4)
gG-10 (0.37–3)
gG-16 (4–7.5)
gG-40
gG-50 (18.5)
gG-63 (22)
gG-40
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
gG-80 (30)
gG-100 (37)
gG-160 (45)
aR-200 (55)
aR-250 (75)
gG-100 (37)
gG-150 (37)
gG-160 (45)
gG-160 (45)
aR-200 (55)
aR-250 (75)
Rev. 2014-04-04 All rights reserved.
Recommended circuit
breaker Moeller
gG-25
PKZM0-10
gG-25
PKZM0-16
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-160
NZMB2-A200
aR-250
NZMB2-A250
NZMB2-A200
aR-250
NZMB2-A250
Max trip level [A]
10
16
25
25
25
63
100
50
100
160
250
9
150
250
135
9