12.7.7 The PKE Field
The PKE field contains two subfields: Parameter command
and response AK, and parameter number PNU:
PKE
IND
AK
PNU
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Figure 12.10 PKE Field
Bits no. 12-15 transfer parameter commands from master
to follower and return processed follower responses to the
master.
Bit no.
Parameter command
15
14
13
12
0
0
0
0
No command
0
0
0
1
Read parameter value
0
0
1
0
Write parameter value in RAM (word)
0
0
1
1
Write parameter value in RAM (double
word)
1
1
0
1
Write parameter value in RAM and
EEPROM (double word)
1
1
1
0
Write parameter value in RAM and
EEPROM (word)
1
1
1
1
Read/write text
Table 12.4 Parameter Commands Master ⇒ Follower
Bit no.
Response
15
14
13
12
0
0
0
0
No response
0
0
0
1
Parameter value transferred (word)
0
0
1
0
Parameter value transferred (double
word)
0
1
1
1
Command cannot be performed
1
1
1
1
text transferred
Table 12.5 Response Follower⇒ Master
MG33BF22
Design Guide
If the command cannot be performed, the follower sends
this response:
0111 Command cannot be performed
- and issues the following fault report in the parameter
value (PWE):
PWE
PWE
high
low
12.7.8 Parameter Number (PNU)
Bits no. 0-11 transfer parameter numbers. The function of
the relevant parameter is defined in the parameter
description in the Programming Guide.
12.7.9 Index (IND)
The index is used together with the parameter number to
read/write-access parameters with an index, e.g.,
15-30 Alarm Log: Error Code. The index consists of two
bytes, a low byte and a high byte.
Only the low byte is used as an index.
Rev. 2014-04-04 All rights reserved.
PWE low
Fault Report
(Hex)
0
The parameter number used does not exist
1
There is no write access to the defined parameter
2
Data value exceeds the parameter's limits
3
The sub index used does not exist
4
The parameter is not the array type.
5
The data type does not match the defined
parameter
11
Data change in the defined parameter is not
possible in the adjustable frequency drive's
present mode. Certain parameters can only be
changed when the motor is turned off
82
There is no bus access to the defined parameter
83
Data change is not possible because factory set-
up is selected
Table 12.6 Parameter Value Fault Report