Control Input/Output And Control Data - Danfoss VLT AutomationDrive FC 301 Series Design Manual

Hide thumbs Also See for VLT AutomationDrive FC 301 Series:
Table of Contents

Advertisement

Product Specifications

6.2.5 Control Input/Output and Control Data

6.2.5.1 Digital Inputs
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
2)
Voltage level, logic '0' NPN
2)
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency ranges
(Duty cycle) Min. pulse width
Input resistance, R
i
3, 4)
Safe stop Terminal 37
(Terminal 37 is fixed PNP logic)
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Maximum voltage on input
Typical input current at 24 V
Typical input current at 20 V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1)
Terminals 27 and 29 can also be programmed as output.
2)
Except safe stop input Terminal 37.
®
3)
See VLT
Adjustable Frequency Drives - Safe Torque Off Instruction Manual for further information about terminal 37 and Safe
Stop.
4)
When using a contactor with a DC coil inside in combination with Safe Stop, it is important to make a return way for the
current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 or 50 V MOV for
quicker response time) across the coil. Typical contactors can be bought with this diode.
MG33BF22
Design Guide
Rev. 2014-04-04 All rights reserved.
1)
1)
FC 301: 4 (5)
/FC 302: 4 (6)
1)
1)
18, 19, 27
, 29
, 32, 33
PNP or NPN
0–24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
0–110 kHz
4.5 ms
Approx. 4 kΩ
0–24 V DC
<4 V DC
>20 V DC
28 V DC
50 mA rms
60 mA rms
400 nF
77
6
6