System Integration
RFI filter type
Standards and
EN 55011/CISPR 11
requirements
EN/IEC 61800-3
H1
0–50 hp [0–37 kW]
FC 301
200–240 V
0–100 hp [0–75 kW]
380–480 V
0–50 hp [0–37 kW]
FC 302
200–240 V
0–100 hp [0–75 kW]
380–480 V
H2/H5
FC 301
0–5 hp [0–3.7 kW]
200–240 V
7.5–50 hp [5.5–37 kW]
FC 302
200–240 V
0–10 HP (0–7.5 kW)
380–500 V
15–100 hp [11–75 kW]
380–500 V
15–30 hp [11–22 kW]
525–690 V
40–100 hp [30–75 kW]
525–690 V
H3
0–2 hp [0–1.5 kW]
FC 301
200–240 V
0–2 hp [0–1.5 kW]
380–480 V
H4
1.5–10 hp [1.1–7.5 kW]
FC 302
525–690 V
15–30 hp [11–22 kW]
525–690 V
15–50 hp [11–37 kW]
525–690 V
40–100 hp [30–75 kW]
525–690 V
Hx
1)
1–100 hp [0.75–75 kW]
FC 302
525–600 V
Table 5.2 EMC Test Results (Emission) Maximum Motor Cable Length
1)
Hx versions can be used according to EN/IEC 61800-3 category C4.
2)
T5, 30–60 hp [22–45 kW] and T7, 30–100 hp [22–75 kW] comply with class A group 1 with 25 m motor cable. Some restrictions for the instal-
lation apply (contact Danfoss for details).
Hx, H1, H2, H3, H4 or H5 is defined in the type code pos. 16-17 for EMC filters, see Table 7.1.
3)
IP20
MG33BF22
Design Guide
Conducted emission
Cable length [m]
Class B
Class A
Group 1
Category C1
Category C2
10
50
10
50
50
150
50
150
No
No
No
No
2)
No
No
No
No
2)
No
No
2)
No
No
2)
2.5
25
2.5
25
No
100
No
100
No
150
3
No
150
No
No
Rev. 2014-04-04 All rights reserved.
Radiated emission
Class A
Class B
Group 2
Category C3
Category C1
50
No
50
No
150
No
150
No
5
No
25
No
5
No
25
No
25
No
25
No
25
No
25
No
100
No
100
No
150
No
150
No
No
No
Class A
Class A
Group 1
Group 2
Category C2
Category C3
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
55
5
5