Electrical Installation
Power
SIBA
[kW]
Type RK1
0.5–1.5
5017906-006
[0.37–1.1]
2–3
5017906-010
[1.5–2.2]
4 [3]
5017906-016
5 [4]
5017906-020
7.5 [5.5]
5017906-025
10 [7.5]
5012406-032
15 [11]
5014006-040
20 [15]
5014006-050
24 [18]
5014006-063
30 [22]
2028220-100
40 [30]
2028220-125
50 [37]
2028220-125
60 [45]
2028220-160
75 [55]
2028220-200
100 [75]
2028220-250
Table 9.11 380–500 V, Enclosure Types A, B and C
Power
Bussmann
[kW]
JFHR2
0.5–1.5
FWH-6
[0.37–1.1]
2–3
FWH-10
[1.5–2.2]
4 [3]
FWH-15
5 [4]
FWH-20
7.5 [5.5]
FWH-25
10 [7.5]
FWH-30
15 [11]
FWH-40
20 [15]
FWH-50
24 [18]
FWH-60
30 [22]
FWH-80
40 [30]
FWH-100
50 [37]
FWH-125
60 [45]
FWH-150
75 [55]
FWH-200
100 [75]
FWH-250
Table 9.12 380–500 V, Enclosure Types A, B and C
1)
Ferraz-Shawmut A50QS fuses may substitute for A50P fuses.
MG33BF22
Design Guide
Recommended max. fuse
Littelfuse
Type RK1
KLS-R-6
KLS-R-10
KLS-R-15
KLS-R-20
KLS-R-25
KLS-R-30
KLS-R-40
KLS-R-50
KLS-R-60
KLS-R-80
KLS-R-100
KLS-R-125
KLS-R-150
KLS-R-200
KLS-R-250
Recommended max. fuse
Ferraz- Shawmut
Ferraz- Shawmut J
HSJ-6
HSJ-10
HSJ-15
HSJ-20
HSJ-25
HSJ-30
HSJ-40
HSJ-50
HSJ-60
HSJ-80
HSJ-100
HSJ-125
HSJ-150
HSJ-200
HSJ-250
Rev. 2014-04-04 All rights reserved.
Ferraz-
Shawmut
Type CC
ATM-R-6
ATM-R-10
ATM-R-15
ATM-R-20
ATM-R-25
ATM-R-30
-
-
-
-
-
-
-
-
-
1)
JFHR2
-
-
-
-
-
-
-
-
-
-
-
-
-
A50-P-225
A50-P-250
Ferraz-
Shawmut
Type RK1
A6K-6-R
A6K-10-R
A6K-15-R
A6K-20-R
A6K-25-R
A6K-30-R
A6K-40-R
A6K-50-R
A6K-60-R
A6K-80-R
A6K-100-R
A6K-125-R
A6K-150-R
A6K-200-R
A6K-250-R
9
Littelfuse
JFHR2
-
-
-
-
-
-
-
-
-
-
-
-
-
L50-S-225
L50-S-250
139