Danfoss VLT AutomationDrive FC 301 Series Design Manual page 87

Hide thumbs Also See for VLT AutomationDrive FC 301 Series:
Table of Contents

Advertisement

Product Specifications
l
(%)
out
NO
110%
100%
90%
80%
60%
40%
20%
0
0
2
4
6
8
10
Figure 6.23 Derating of I
for different T
out
enclosure types C3 and C4, using 60° AVM in Normal
overload mode (110% overtorque)
SFAVM - Stator Frequency Asyncron Vector Modulation
I
(%)
out
HO
110%
100%
80%
60%
40%
20%
0
0
2
4
6
8
10
Figure 6.24 Derating of I
for different T
out
enclosure types C1 and C2, using SFAVM in High
overload mode (160% overtorque)
I
(%)
out
NO
110%
100%
80%
60%
40%
20%
0
0
2
4
6
8
Figure 6.25 Derating of I
for different T
out
enclosure types C1 and C2, using SFAVM in Normal
overload mode (110% overtorque)
MG33BF22
Design Guide
C3 & C4
o
45 C
o
50 C
o
55 C
f
(kHz)
sw
12
14
16
for
AMB, MAX
C1 & C2
45°C
50°C
55°C
f
(kHz)
sw
12
14
16
for
AMB, MAX
C1 & C2
45°C
50°C
55°C
f
(kHz)
sw
10
12
14
16
for
AMB, MAX
Rev. 2014-04-04 All rights reserved.
l
(%)
out
HO
110%
100%
90%
80%
o
45 C
60%
o
50 C
40%
20%
0
0
2
4
6
8
10
Figure 6.26 Derating of I
for different T
out
enclosure types C3 and C4, using SFAVM in High overload
mode (160% overtorque)
l
(%)
out
NO
110%
100%
90%
80%
60%
o
45 C
o
50 C
40%
20%
0
0
2
4
6
8
10
Figure 6.27 Derating of I
for different T
out
enclosure types C3 and C4, using SFAVM in Normal overload
mode (110% overtorque)
C3 & C4
f
(kHz)
sw
12
14
16
for
AMB, MAX
C3 & C4
f
(kHz)
sw
12
14
16
for
AMB, MAX
85
6
6

Advertisement