7.2.8 Sine-Wave Filters

Adjustable frequency drive power and current ratings
200–240 V
380–440 V
(hp
(hp
[A]
[kW])
[kW])
0.5
-
-
[0.37]
0.34
0.75
1.8
[0.25]
[0.55]
0.5
2.4
1 [0.75]
[0.37]
1.5 [1.1]
0.75
3.5
2 [1.5]
[0.55]
1 [0.75]
4.6
3 [2.2]
1.5 [1.1]
6.6
4 [3]
2 [1.5]
7.5
-
-
-
5 [4]
3 [2.2]
10.6
7.5 [5.5]
4 [3]
12.5
10 [7.5]
5 [3.7]
16.7
-
7.5 [5.5]
24.2
15 [11]
20 [15]
10 [7.5]
30.8
25
[18.5]
15 [11]
46.2
30 [22]
20 [15]
59.4
40 [30]
25
74.8
50 [37]
[18.5]
30 [22]
88
60 [45]
40 [30]
115
75 [55]
50 [37]
143
100 [75]
60 [45]
170
125 [90]
Table 7.26 Sine-Wave Filters for Adjustable Frequency Drives with 380–500 V
1)
Ordering numbers marked with * are IP23.
MG33BF22
Design Guide
441–500 V
50 Hz
(hp
[A]
[A]
[kW])
0.5
1.3
1.1
[0.37]
0.75
1.8
1.6
[0.55]
2.4
1 [0.75]
2.1
3
1.5 [1.1]
3
4.1
2 [1.5]
3.4
5.6
3 [2.2]
4.8
7.2
4 [3]
6.3
-
-
-
10
5 [4]
8.2
13
7.5 [5.5]
11
16
10 [7.5]
14.5
-
-
-
24
15 [11]
21
32
20 [15]
27
25
37.5
34
[18.5]
44
30 [22]
40
61
40 [30]
52
73
50 [37]
65
90
75 [55]
80
106
100 [75]
105
147
125 [90]
130
177

Rev. 2014-04-04 All rights reserved.

Switching
Filter current rating
frequency
60 Hz
100 Hz
[A]
[A]
[A]
2.5
2.5
2
4.5
4
3.5
8
7.5
5.5
10
9.5
7.5
17
16
13
24
23
18
38
36
28.5
48
45.5
36
62
59
46.5
75
71
56
115
109
86
180
170
135
Ordering no.
IP00
IP20/23
[kHz]
5
130B2404
130B2439
5
130B2406
130B2441
5
130B2408
130B2443
5
130B2409
130B2444
5
130B2411
130B2446
4
130B2412
130B2447
4
130B2413
130B2448
4
130B2281
130B2307
3
130B2282
130B2308
3
130B2283
130B2309
3
130B3179
130B3181*
3
130B3182
130B3183*
1)
7
7
113