Options and Accessories
Digital input - terminal X30/1-4
Number of digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP (GND = 0 V)
Voltage level, logic'1' PNP (GND = 0 V)
Voltage level, logic '0' NPN (GND = 24 V)
Voltage level, logic '1' NPN (GND = 24 V)
Maximum voltage on input
Pulse frequency ranges
Duty cycle, min. pulse width
Input impedance
Analog input - terminal X30/11, 12
Number of analog inputs
Terminal number
Modes
Voltage level
Input impedance
Max. voltage
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
Digital outputs - terminal X30/6, 7
Number of digital outputs
Terminal number
Voltage level at digital/frequency output
Max. output current
Max. load
Max. capacitive load
Minimum output frequency
Maximum output frequency
Accuracy of frequency output
Analog output - terminal X30/8
Number of analog outputs
Terminal number
Current range at analog output
Max. load GND - analog output
Accuracy on analog output
Resolution on analog output
MG33BF22
Design Guide
Rev. 2014-04-04 All rights reserved.
3
X30.2, X30.3, X30.4
PNP or NPN
0–24 V DC
< 5 V DC
> 10 V DC
< 14 V DC
> 19 V DC
28 V continuous
0–110 kHz
4.5 ms
> 2 kΩ
2
X30.11, X30.12
Voltage
0–10 V
> 10 kΩ
20 V
10 bit (+ sign)
Max. error 0.5% of full scale
FC 301: 20 Hz/ FC 302: 100 Hz
2
X30.6, X30.7
0–24 V
40 mA
≥ 600 Ω
< 10 nF
0 Hz
≤ 32 kHz
Max. error: 0.1% of full scale
1
X30.8
0–20 mA
500 Ω
Max. error: 0.5% of full scale
12 bit