Options and Accessories
Input voltage (DC)
Typical current input (DC)
Max. current input (DC)
Max. current inrush (DC)
Output voltage (DC)
Turn on delay
Turn off delay
Observe the following precautions
The FC 302 with MCB 108 (including the connections between X31/9 and Terminal 37) must be placed inside an
IP54 enclosure.
Safe Stop activation (i.e., removal of 24 V DC voltage supply to terminal 37 by removing voltage to dual pole input
of MCB 108) does not provide electrical safety.
The safety device connected to the dual pole input of the MCB 108 must fulfill the requirements of cat. 3 / PL d
according to ISO 13849-1 for interrupting the voltage/current to the MCB 108. This also applies for the connections
between the MCB 108 and the safety device.
Read and follow the instructions for the safety device to connect it properly to MCB 108.
Figure 11.13 Option Module Safe PLC Interface MCB 108
MCB 108
Safe PLC
24 V DC
X31/2
P - Control
P - Monitor
X31/3
GND
M - Monitor
M - Monitor
GND
Figure 11.14 Safe PLC Interface MCB 108 Connection
MG33BF22
Design Guide
FC 302
X31/9
37
Safe
channel
X31/10
20
GX
Rev. 2014-04-04 All rights reserved.
18–28 V DC
60 mA
110 mA DC
500 mA DC
20 V DC@Vin = 24 V
1 ms
3 ms
11
171
11