7.1.1.4.3 "Scaling" Menu Item - WAGO 750-496 Manual

8ai 0/4-20ma s.e., 8-channel analog input; 0/4-20 ma, single-ended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Table 28: Channel settings Menu Item
Option
Show measurement
underrange
Show overrange of user
range values
Show underrange of
user range values
Show short circuit
Show wire break
Specifying Limiting Values
Upper limit
Lower limit
Offset for Measurement Range Monitoring
Offset for diagnosis
measurement overrange
Offset for diagnosis
measurement
underrange
*)
Factory setting

7.1.1.4.3 "Scaling" Menu Item

Save settings!
Click the [Write] or [Write all
I/O module.
Description
*)
The "Measurement Underrange" diagnosis function is activated
and is displayed in the status byte.
The "Measurement Underrange" diagnostics function is
deactivated and is not displayed in the status byte.
*)
The "User limiting value overrange" diagnosis function is
activated and is displayed in the status byte.
The "User limiting value overrange" diagnosis function is
deactivated and is not displayed in the status byte.
*)
The "User limiting value underrange" diagnosis function is
activated and is displayed in the status byte.
The "User limiting value underrange" diagnosis function is
deactivated and is not displayed in the status byte.
*)
The "Display short circuit" diagnosis function is activated and is
displayed in the status byte.
The "Display short circuit" diagnosis function is deactivated and
is not displayed in the status byte.
*)
The "Show wire break" is activated and is displayed in the status
byte.
The "Show wire break" diagnosis function is deactivated and is
not display status byte.
Enter the upper limiting value of your required value range.
The value entered must fall within the value range −32768 ... +32767.
Enter the lower limiting value of your required value range.
The value entered must fall within the value range −32768 ... +32767.
Enter the offset value at which the "Measurement Range Overrange"
diagnostic message should be triggered.
Note: When selecting the sensor type 3.6 ... 21mA (NAMUR NE43), you
are not permitted to determine this value.
Enter the offset value at which the "Measurement Range Underrange"
diagnostic message should be triggered.
Note: When selecting the sensor type 3.6 ... 21mA (NAMUR NE43), you
are not permitted to determine this value.
]
button to write any settings you have made to the
Commissioning
55