Q4: How to write data to output channels on a Modbus RTU slave device? 
A4:   
 
Step 1: Edit the polling definition for the output channels with read function code in the 
config.csv file. (For example, use 01 to read DO channels, 03 to read AO channels) 
 
UseComPort SlaveModbusID FunctionCode RegStartAddr RegCount
 
 
Step 2: Import the config.csv file into the MDC‐700, wait the MDC‐700 reboot in 5 seconds, and 
then check the addresses for the local registers mapped to the output channels. 
Step 3: Write data with corresponding function code (05/06/15/16) on your Modbus master device 
to the local registers mapped for the output channels, the MDC‐700 will process writing 
operations to the slave devices. 
 
 
 
 
 
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved.  ∗  E‐mail: service@icpdas.com                                          ‐ 32 ‐ 