Table 27: QFX5200 Switch Environmental Tolerances
Description
Temperature
Seismic
NOTE: Install QFX Series devices only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.
General Site Guidelines
Efficient device operation requires proper site planning and maintenance and proper layout of the
equipment, rack or cabinet, and wiring closet.
To plan and create an acceptable operating environment for your device and prevent environmentally
caused equipment failures:
• Keep the area around the chassis free from dust and conductive material, such as metal flakes.
Model
QFX5200-32C and
QFX5200-32C-L
QFX5200-48Y
QFX5200 all models
(Continued)
Tolerance
•
Normal operation ensured in temperature range
of 32° F through 104° F (0° C through 40° C)
•
Nonoperating storage temperature in shipping
container: –40° F through 158° F (–40° C
through 70° C)
•
Normal operation ensured in temperature range
of 32° F through 113° F (0° C through 45° C) for
AFO models, 32° F through 104° F (0° C
through 40° C) for AFI models
•
Nonoperating storage temperature in shipping
container: –40° F through 158° F (–40° C
through 70° C) for both AFO and AFI
Designed to comply with Zone 4 earthquake
requirements per NEBS GR-63-CORE, Issue 3.