Table 18: QFX5130-32CD Switch Environmental Tolerances
Description
Altitude
Relative humidity, operating
Temperature
Seismic
General Site Guidelines
Efficient device operation requires proper site planning and maintenance. It also requires proper layout
of the equipment, rack or cabinet, and wiring closet.
To plan and create an acceptable operating environment for your device and prevent environmentally
caused equipment failures:
Tolerance
•
QFX5130-32CD-AFO–At 32° F through 104° F (0° C through
40° C) there is no performance degradation to 6000 feet
(1828.8 meters)
•
QFX5130-32CD-AFI-At 32° F through 77° F (0° C through 25° C)
there is no performance degradation to 6000 feet (1828.8 meters)
Normal operation ensured in relative humidity range of 5% through
90%, noncondensing
QFX5130-32CD-AFO
•
Normal operation ensured in temperature range of 32° F through
104° F (0° C through 40° C)
•
Nonoperating storage temperature in shipping container: –40° F
through 158° F (–40° C through 70° C)
QFX5130-32CD-AFI
•
Normal operation ensured in temperature range of 32° F through
77° F (0° C through 40° C)
•
Nonoperating storage temperature in shipping container: –40° F
through 158° F (–40° C through 70° C)
Designed to comply with Zone 4 earthquake requirements per NEBS
GR-63-CORE, Issue 3.
39