Commissioning
6. Commissioning
6.1 Commissioning flow chart insulation fault monitoring
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
System = IT system ?
yes
U
< AC 1000/DC 1500 V ?
n
yes
U
< AC 2000/DC3 000 V ?
n
Deenergize the installation before
yes
connecting the device
Device connection
(see chapter Connection)
Connect supply voltage
Connect system voltage
The iso1685Dxx successfully
carries out a self test
yes
Use the commissioning wizard to
set the device parameters
(see chapter initial commissioning)
Alarm LEDS activated?
no
Function test with a suitable
resistance between system and
earth. Value: 50% of the response
value Ran2
Alarm LEDs activated?
Alarm relays switched?
yes
Remove resistance
Alarm LEDs extinguished?
Alarm relays switched?
The iso1685Dxx is correctly
connected and functions reliably
no
iso1685Dxx not suitable
iso1685DP not suitable,
no
check if iso1685D-HV is suitable
no
iso1685D-HV not suitable
Connection or device error:
no
Check connections
Preset response value
yes
undershot, possibly adjust
Check connections
no
no
29