Function
3.5.2
Automatic self test
All supply voltages are continuously monitored. The following tests are continuously carried
out in the background:
E-KE connection
Temperature monitoring of coupling and locating current injector
A self test is automatically run at 24-hour intervals.
During the automatic self test, the alarm relays K1 (11-12-14) and K2 (21-22-24) are not swit-
ched. K3 will not be switched either.
3.5.3
Manual self test
The self test is started via the TEST button of the ISOMETER®.
The following tests are only carried out in the manual self test mode:
Internal flash
CPU register
Watchdogs
Oscillator
Restart of the device including re-initialisation and recalibration
Connection monitoring system
During the manual self test, all alarm relays are switched.