Function
3. Function
3.1 Features
ISOMETER® for AC IT systems with galvanically connected rectifiers or inverters and for DC IT
systems. (IT = unearthed systems)
•
Automatic adjustment to high system leakage capacitances, for measuring ranges
see
11. "Alarm messages" on page 74
•
Combination of AMP
•
Separately adjustable response values R
and alarm
•
High-resolution graphic LC display for excellent readability and recording of the device
status
•
Connection monitoring
•
Automatic device self test with automatic alarm message in the event of a fault
•
Graphical representation of the insulation resistance over time (isoGraph)
•
History memory with real-time clock (buffer for 13 days) for storing 1023 alarm messa-
ges with date and time
•
Freely programmable digital inputs/outputs
•
Remote setting of certain parameters via the Internet (COMTRAXX® gateway)
•
Remote diagnosis by the Bender service via the Internet
•
RS-485 interface for data exchange with other Bender devices
iso1685DP-425
•
Measurement of insulation faults 200 Ω...1 MΩ
•
Integrated locating current injector up to 50 mA for insulation fault location
•
Display of insulation faults selectively located by EDS systems
•
Parameter setting of EDS systems
•
Customer-specific texts for each measuring channel via the menu
isoLR1685DP-425
•
Measurement of low-resistance insulation faults 20 Ω...100 kΩ
•
Integrated locating current injector up to 50 mA for insulation fault location
•
Display of insulation faults selectively located by EDS systems
•
Parameter setting of EDS systems
•
Customer-specific texts for each measuring channel via the menu
isoHV1685D-425
•
Measurement of insulation faults 200 Ω...1 MΩ in IT systems with mains voltages
of AC 2000 V and DC 3000 V
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
PLUS
and other profile-specific measurement method
(alarm 1) and R
an1
(alarm 2) for prewarning
an2