Settings
8.2
(2.4.3) Dig. input
Select the digital inputs of the EDS to be configured:
•Select all
•No selection
•Invert selection
•Dig. input 1 (BS 2/1)
•Dig. input 2 (BS 2/2)
Afterwards, make the settings for the selected digital inputs of the EDS.
8.2
(2.4.3.1) Mode
The operating mode for the digital input can be set to the values below. For a description, refer
to
"Setting the EDS mode (isoxx1685DP only)" on page
•Active high
•Active low
8.2
(2.4.3.2) t(on)
The response time t(on) after a switch-on signal can be set between 100 milliseconds and 5 mi-
nutes. For a description, refer to
8.2
(2.4.3.3) t(off)
The response time t(off) after a switch-off signal can be set between 100 milliseconds and 5
minutes. For a description, refer to
8.2
(2.4.3.4) Function
•off
•TEST
•RESET
8.2
(2.4.4) Device settings
•Select all
•No selection
•Invert selection
•BMS bus 2 (1-12)
8.2
(2.4.4.1) System type
Adjust the EDS to the IT system to be monitored.
•DC
•AC
•3AC
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
All digital inputs are selected.
No digital input is selected.
The current selection is inverted.
A single digital input is selected.
An event is carried out on the falling edge of the digital input (low to high).
An event is carried out on the falling edge of the digital input (high to low).
"Setting the EDS mode (isoxx1685DP only)" on page
"Setting the EDS mode (isoxx1685DP only)" on page
Digital input without function
Device self test
Reset of fault and alarm messages
All devices are selected.
No device is selected.
The current selection is inverted.
DC system
Single-phase AC system
3AC system
33. The following can be selected
:
33.
33.
57

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ISOMETER iso1685DP-425 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Isometer isohv1685d-425Isometer isolr1685dp-325

Table of Contents