Bender ISOMETER iso1685DP-425 Manual page 49

Insulation monitoring device for unearthed ac, ac/dc and dc power supplies it systems
Hide thumbs Also See for ISOMETER iso1685DP-425:
Table of Contents

Advertisement

Settings
8.2
(1.7.4.2) Function 1
The following parameters can be set:
•off
•Ins. alarm 1
•Ins. alarm 2
•Connection fault
•Device error
•Common alarm
•Device inactive
8.2
(1.7.4.3) Function 2
See
chapter 8.2 (1.7.4.2) "Function
8.2
(1.7.4.4) Function 3
See
chapter 8.2 (1.7.4.2) "Function
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
The function is not used.
The status of the output changes when the value falls below the set
response value R
an1.
The status of the output changes when the value falls below the set
response value R
an2.
The status of the output changes when one of the following connec-
tion faults occurs:
• No low-resistance connection between the line conductors.
• No low-resistance connection of terminals E and KE to earth (PE).
The status of the output changes in the event of an internal device
error.
The status of the output changes on the occurrence of any alarm
and fault messages
(Ins. alarm 1 & 2, DC-/DC+ alarm, symmetrical alarm, connection
faults and device errors).
The status of the output changes when the device has been deacti-
vated via a digital input or the control menu.
1".
1".
49

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ISOMETER iso1685DP-425 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Isometer isohv1685d-425Isometer isolr1685dp-325

Table of Contents