Settings
8.2
(1.7.4.2) Function 1
The following parameters can be set:
•off
•Ins. alarm 1
•Ins. alarm 2
•Connection fault
•Device error
•Common alarm
•Device inactive
8.2
(1.7.4.3) Function 2
See
chapter 8.2 (1.7.4.2) "Function
8.2
(1.7.4.4) Function 3
See
chapter 8.2 (1.7.4.2) "Function
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
The function is not used.
The status of the output changes when the value falls below the set
response value R
an1.
The status of the output changes when the value falls below the set
response value R
an2.
The status of the output changes when one of the following connec-
tion faults occurs:
• No low-resistance connection between the line conductors.
• No low-resistance connection of terminals E and KE to earth (PE).
The status of the output changes in the event of an internal device
error.
The status of the output changes on the occurrence of any alarm
and fault messages
(Ins. alarm 1 & 2, DC-/DC+ alarm, symmetrical alarm, connection
faults and device errors).
The status of the output changes when the device has been deacti-
vated via a digital input or the control menu.
1".
1".