Output values

Output
Analog (BAO)
0-10 Vdc
2-10 Vdc
Binary (BBO)
Relay
Universal (BBO or BAO)
0-10 Vdc
2-10 Vdc
Relay
12 Vdc PWM
1
The Analog Output microblock uses the Min and Max values to linearly translate its incoming value into a
physical output signal (Volts) sent from the TV-UCXP683T to a device. For example, set Min to 0 and Max to 100
for an Analog Output microblock that receives a 0 to 100% open signal from a PID microblock and that controls
a 0–10 Vdc actuator so that when the PID signal is 100%, the TV-UCXP683T output is 10 Vdc. Similarly, when
the PID signal is 50%, the TV-UCXP683T output is 5 Vdc.
TruVu™ UCXP683T
Installation and Start-up Guide
I/O Type
Sensor/Actuator Type
Electrical
Linear Full Range
0–10 Volt
No Translation
Electrical
Linear w/Offset,
0–10 Volt
2–10 Volts
Relay/Triac
N/A
Output
Electrical
Linear Full Range
0–10 Volt
No Translation
Electrical
Linear w/Offset,
0–10 Volt
2–10 Volts
Relay/Triac
N/A
Output
PWM 80 Hz
No Translation
Min/Max
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
N/A. The Analog Output microblock will
output the same value that comes in to
the microblock.
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
N/A
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
N/A. The Analog Output microblock will
output the same value that comes in to
the microblock.
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
N/A
0% (Min) and 100% (Max). The Analog
Output microblock will vary the width of
the pulse based on the value that
comes into the microblock.
29
To adjust input and output properties
1
1
CARRIER CORPORATION ©2022
All rights reserved