The MPC Open XP and expanders have universal outputs that you can use as binary outputs or analog outputs.
The outputs support:
driving external 24 Vdc relays
0-10 Vdc devices
0-20 mA devices
WARNING Binary outputs are powered, 24 Vdc channels. Dry contact binary outputs are not supported in
this product line. Do NOT apply 24 Vac to these universal outputs.
If output controls a...
0–10 Vdc device
0–20 mA device
NOTES
The device must share the same ground as the controller.
The total output current from all outputs and the Aux Power Out connection must not exceed:
500 mA at 115°F
300 mA at 140°F
For temperatures above 115°F, use the following equation to calculate the total current at 8 mA per degree:
500mA - ((max. expected temp. - 115°F) * 8mA)

Output wiring specifications

To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
MPC Open XP
MPC Open XP IO48/816
Installation and Start-up Guide
Maximum length
500 feet
(152 meters)
500 feet
(152 meters)
Resistance to ground must be...
500 Ohms minimum
800 Ohms maximum
Carrier Proprietary and Confidential
15
Minimum gauge
Shielding
22 AWG
Shielded or
unshielded
22 AWG (7x0096) bare
If shielded, Aluminum/Mylar
copper
shield (100% coverage) with TC
drain wire
Installing the MPC Open XP