Parameters Required For Snmp Via Ethernet; Snmp Trap Messages - Datakom D-500 MK2 User Manual

Advanced genset controller
Table of Contents

Advertisement

D-500 MK2 User Manual

36.1. PARAMETERS REQUIRED FOR SNMP VIA ETHERNET

Modbus Slave Address: may be set between 1 and 240. If only one unit is available in the same IP
address, it is advised to keep the default address (1).
Ethernet Enable: This parameter should be set to 1 (or checked) in order to enable the ethernet port.
Modbus TCP/IP Port: The usual setting is 502. However the unit is able to work on any port address.
User IP Mask: There are 3 mask registers available. The use of the registers are emphasized in the
D500 User Manual. Please set the first mask as 255.255.255.0 for the proper operation.
Ethernet Network IP: May be left as 0.0.0.0 for automatic address claim or set to a value in order to
claim a defined address.
Ethernet Gateway IP: Should be set in accordance with your local switch configuration.
Ethernet Subnet Mask: Should be set in accordance with your local switch configuration.

36.2. SNMP TRAP MESSAGES

When a fault case occurs or the genset runs or the genset takes the load or the genset unloads or the
genset stops, an automatic SNMP TRAP message is send to the SNMP Client.
In order to enable SNMP TRAP messages, the Client has to send at least one SNMP request message to
the controller in order to inform it about its IP address. The controller records the address of the last
SNMP Client and sends trap messages to this address.
The SNMP TRAP message message contains the controller operating mode, engine status and the alarm
list.