Ethernet Configuration - Datakom D-500 MK2 User Manual

Advanced genset controller
Table of Contents

Advertisement

D-500 MK2 User Manual

18. ETHERNET CONFIGURATION

Related parameters are:
Parameter Definition
Network IP Address
Gateway IP Address
Subnet Mask
Modbus TCP/IP Port
Modbus Address
The ethernet connection status is monitored at ethernet screen page.
Connection
status
indicator
Factory Set
This is the IPv4 (internet protocol version 4) address
that the unit will require from the DHCP (dynamic host
control protocol) server.
0.0.0.0
If this parameter is set to 0.0.0.0 then the unit will
require any IPv4 address from the DHCP server.
If you are not an IP professional please leave this
address as "0.0.0.0".
This is the router IPv4 address, If the Network IP
address and Gateway IP Address are set to "0.0.0.0"
then the unit will get the gateway address
0.0.0.0
automatically.
If you are not an IP professional please leave this
address as "0.0.0.0".
Reserved for IP professionals.
255.255.255.0
If you are not an IP professional please leave this
address as "255.255.255.0".
Internal Modbus TCP/IP server's port number. The unit
502
answers Modbus requests to this port only.
This is the modbus controller identity used in Modbus
1
communication.
- 140 -
Firmware V-6.3
Description
IP address
of the unit,
assigned by
the network
switch
Data Receive
and Transmit
Indicators