20. GSM CONFIGURATION

Related parameters are:
Parameter Definition
SMS Enable
GPRS Connection
Enable
SMS on Mains
Change
SMS on Engine
Run/Stop
SMS Commands
Enabled
GSM Location Active
APN User Name
APN Password
APN Name
Signal Strenght
Indicator
IP address
Factory Set
0
0
0
0
0
0
The APN (access point name) username may be required by the GSM
operator. However some GSM operators may allow access without username.
The exact information should be obtained from the GSM operator.
Please search the GSM operator's website with "APN" string.
If the APN (access point name) username is required by the GSM operator,
most probably the APN password will also be required. However some GSM
operators may allow access without password.
The exact information should be obtained from the GSM operator.
Please search the GSM operator's website with "APN" string.
The APN (access point name) is always required by the GSM operator.
The exact information should be obtained from the GSM operator.
Please search the GSM operator's website with "APN" string.
RainbowScada
packet counter
- 142 -
Description
0: SMS messages disabled
1: SMS messages enabled
0: GPRS disabled
1: GPRS enabled
This parameter controls SMS sending when mains
voltages status is changed. No warnings generated.
0: no SMS on mains failed or restored
1: SMS sent on mains failed or restored
This parameter controls SMS sending when the engine
runs or stops. No warnings generated.
0: no SMS on engine run/stop
1: SMS sent on engine run/stop
0: SMS commands not accepted
1: SMS commands are accepted but from listed
telephone numbers only.
0: no location information from GSM
1: location information read from GSM system.
Firmware V-6.3