24. AUTO LEARNING

The controller offers the automatic learning feature for adjusting synchronization & load sharing set-points
and PID coefficients.
The AUTO LEARNING makes the synchronization commissioning and fine adjusting a simple
straightforward operation.
In order to activate the AUTO LEARNING:
Please enter programming > synchronization parameters.
Disable GOV control enable parameter.
Gov Low Limit will be 0, Gov Gain will be 100 and Gov rest point will be 50.
Disable AVR control enable parameter.
AVR Low Limit will be 0, AVR Gain will be 100 and AVR rest point will be 50.
Start the generator manually.
Adjust the required nominal frequency on the speed control unit using the speed pot.
Adjust the required nominal voltage on the AVR unit using the voltage pot.