24. AUTO LEARNING
The controller offers the automatic learning feature for adjusting synchronization & load sharing set-points
and PID coefficients.
The AUTO LEARNING makes the synchronization commissioning and fine adjusting a simple
straightforward operation.
In order to activate the AUTO LEARNING:
Please enter programming > synchronization parameters.
▪
Disable GOV control enable parameter.
▪
Gov Low Limit will be 0, Gov Gain will be 100 and Gov rest point will be 50.
▪
Disable AVR control enable parameter.
▪
AVR Low Limit will be 0, AVR Gain will be 100 and AVR rest point will be 50.
Start the generator manually.
▪
Adjust the required nominal frequency on the speed control unit using the speed pot.
▪
Adjust the required nominal voltage on the AVR unit using the voltage pot.