17. PROGRAM PARAMETER LIST

17.1. CONTROLLER CONFIGURATION GROUP

Parameter Definition
LCD Contrast
Screen Scroll Timer
Language
Genset Default Display
Status Prompt Window
Enable
Fault Holdoff Timer
Alarm Relay Timer
Intermittent Alarm Relay
Emergency Backup
Operation
Exerciser Enable
Exercise Period
Exercise Off/On Load
Delayed Simulate Mains
Unit
Min
Max
-
30
50
sec
0
250
-
0
1
-
0
4
-
0
1
sec
0
120
sec
0
120
-
0
1
-
0
1
-
0
1
-
Weekly Monthly Weekly
-
0
1
-
0
1
- 98 -
Factory
Set
This parameter is used to set LCD
31
contrast. Adjust for the best viewing
angle.
The screen will scroll between different
measurements with this interval. If set
0
to zero, the screen scroll will be
disabled.
0: English language selected.
1: Local language selected. This
0
language may depend on the country
where the unit is intended to be used.
This parameter selects the screen
which is displayed during genset on
load operation.
0: genset voltages table
0
1: genset currents and freq. table
2: genset kW and pf table
3: genset kVA and kVAr table
4: genset average measurements
0: Status prompts disabled
0
1: Status prompts enabled
This parameter defines the delay after
12
the engine runs and before the fault
monitoring is enabled.
This is the period during which the
ALARM relay is active. If the period is
60
set to 0, this will mean that the period is
unlimited.
0: continuous
0
1: intermittent (turns on and off every
second)
0: In RUN mode, the load will not be
transferred to the genset even if the
mains fails.
0
1: In RUN mode, the load will be
transferred to the genset if the mains
fails.
0: automatic exerciser disabled
0
1: automatic exerciser enabled
Weekly: exercise once per week
Monthly: exercise once per month
The exact exerciser day and time is
adjusted within the EXERCISE
SCHEDULE section.
0: Exercise at RUN mode
1
1: Exercise at TEST mode
0: delayed simulate mains disabled
0
1: delayed simulate mains enabled
Firmware V-6.3