3.12. J1939-CANBUS PORT

Structure:
Connection:
Data rate:
Termination:
Common mode voltage:
Max distance:

3.13. USB DEVICE PORT

Description:
Data rate:
Connector:
Cable length:
Functionality:
The USB-Device port is designed to connect the module to a PC. Using the RainbowPlus software,
programming, control of the genset and monitoring of measured parameters are achieved.
The RainbowPlus software can be downloaded from Datakom website.
The connector on the module is of USB-B type. Thus, A to B type USB cable should be used. This is the
same cable used for USB printers.
For more details about programming, control and monitoring please refer to RainbowPlus user manual.
If USB-Device is plugged then USB-Host port will not
function.
CANBUS, non-isolated.
3 wires (CANH-CANL-GND).
250 kbps
Internal 120 ohms provided
-0.5 VDC to +15 VDC, internally clamped by transient suppressors.
200m with 120 ohm balanced cable
USB Device
Connector
USB 2.0, not isolated, HID mode
Full Speed 1.5/12 Mbits/s, auto detecting
USB-B (printer connector)
Max 6m
Modbus, FAT32 for firmware upgrade (boot loader mode only)
- 26 -
Firmware V-6.3
USB A to B
Cable