3.8. DIGITAL OUTPUTS

The unit offers 6 digital outputs with programmable function, selectable from list.
Structure:
Max continuous current:
Max switching voltage:
Overvoltage protection:
Short circuit protection:
Reverse voltage
protection:

3.9. MAINS CONTACTOR OUTPUT

Structure:
Max switching current:
Max switching voltage:
Max switching power:

3.10. GENERATOR CONTACTOR OUTPUT

Structure:
Max switching current:
Max switching voltage:
Max switching power:
Negative pulling protected semiconductor output. One terminal is
connected to battery negative.
1.0 ADC
33 VDC
40 VDC
> 1.7 ADC
500 VDC
Relay output, normally closed contact. One terminal is internally
connected to mains phase L1 input.
12A @250VAC
440VAC
3000VA
Relay output, normally open contact. One terminal is internally
connected to genset phase L1 input.
16A @250VAC
440VAC
4000VA