17.8. DIGITAL INPUT CONFIGURATION

The unit has 8 digital inputs. By using external input extension modules, up to 40 inputs in total are
available.
Only parameters of one input are explained below. Other inputs have identical parameter set.
The input name is freely programmable, thus the input can be adapted to any functionality through
programming.
The input name entry is made through RainbowPlus
program only.
Each sender has below programmable parameters:
Parameter Definition
Input Function
Action
Sampling
Latching
Contact type
Switching
Response delay
Unit
Min
Max
-
0
99
-
0
3
-
0
3
-
0
1
-
0
1
-
0
1
-
0
3
- 124 -
Factory
Set
Selects between predefined input
functions. Selected input name is
displayed in the line below.
If this parameter is set to 0 then the
input name string can be freely entered.
0: shutdown alarm
1: loaddump alarm
2: warning
3: no fault condition from this input.
0: always
1: on engine running
2: after hold-off timer
3: reserved
0: non-latching. The fault disappears
when cause is removed.
1: latching. The fault persists even if the
cause is removed. Requires manual
reset.
0: Normally open
1: Normally closed
0: Battery negative
1: Battery positive
0: No delay
1: Delayed (1sec)
2: Delayed (10sec)
3: Delayed (1800sec)
Firmware V-6.3