3. TERMINAL DESCRIPTIONS

3.1. BATTERY VOLTAGE INPUT

Supply voltage:
Cranking dropouts:
Overvoltage protection:
Reverse voltage:
Maximum operating
current:
Typical operating current:
Measurement range:
Display resolution:
Accuracy:
9 to 36VDC
Survives 0VDC during 100ms. The voltage before surge should be
9VDC minimum
Withstands 150VDC continuously.
-36VDC continuous
600mA @ 12VDC. (All options included, digital outputs open.)
300mA @ 24VDC. (All options included, digital outputs open.)
300mA @ 12VDC. (all options passive, digital outputs open)
150mA @ 24VDC. (all options passive, digital outputs open)
0 to 36VDC
0.1VDC
0.5% + 1 digit @ 24VDC
- 17 -