12. DISPLAYING EVENT LOGS

The unit features more than 400 event logs with date-time stamp and full snapshot of measured values at
the moment that the event has occurred.
Stored values in an event record are listed below:
-event number
-event type / fault definition (see below for various event sources)
-date and time
-operation mode
-operation status (on-load, on-mains, cranking, etc...)
-engine hours run
-mains phase voltages: L1-L2-L3
-mains frequency
-genset phase voltages: L1-L2-L3
-genset phase currents: L1-L2-L3
-genset frequency
-genset total active power (kW)
-genset total power factor
-oil pressure
-engine temperature
-fuel level
-oil temperature
-canopy temperature
-ambient temperature
-engine rpm
-battery voltage
-charge voltage
Possible event sources are various. Every source can be individually enabled or disabled:
Event enable
selection tab
Program mode entrance event: recorded with the password level when program mode is entered.
Periodic event: recorded every 30 minutes when the engine is running, and every 60 minutes anyway.
Mode change event: recorded when the operation mode is changed.
Shutdown/loaddump/warning events: recorded when the related fault condition occurs.
Mains fail/restore events: recorded when mains status is changed
Engine started/stopped events: recorded when engine status is changed
Genset on_load/off_load events: recorded when the genset loading status is changed