17.17. SYNCHRONIZATION PARAMETERS

Parameter Definition
Genset Active Power
Rate
Genset Reactive Power
Rate
Mains Active Power Rate
Mains Reactive Power
Rate
Unit Datalink Address
Device Run/Stop Priority
Datalink Baud Rate
Genset Number in Multi
Genset Systems
Minimum Genset Fault
Action
Mains Synch Unit
Number
Master Change Delay
Multi Genset Start-Up
Options
Multi Genset Start-Up
Power
Insufficient Multi Genset
Start-Up Power Alarm
Level
Unit
Min
Max
kW
1
65000
kVAr
1
65000
kW
0
65000
kVAr
0
65000
-
1
64
-
1
64
Kbps
0
4
-
1
48
-
0
4
-
0
16
hour
0
255
-
0
2
kW
0
65000
-
0
3
- 133 -
Factory
Description
Set
It defines genset active power rating.
100
It defines genset reactive power rating.
75
It defines mains transformer active
100
power rating.
It defines mains transformer reactive
75
power rating.
This parameter is used in order to force
data link addresses for fault free
1
operation with broken communication
wires.
This parameter defines the priority level
1
of D500 on the same data link.
0: 50 Kbps
1: 100 Kbps
3
2: 125 Kbps
3: 250 Kbps
4: 500 Kbps
This is the number of synchronizing
1
gensets to the busbar.
This is action to be taken if the number
of available gensets is less than Genset
Number in Multi Genset Systems
0
0: not used
1: engine shutdown
2: load-dump alarm
3: warning
This is the number of Mains
0
Synchronizing units in the system.
This parameter defines the minimum
time period difference between two
0
master change operations in equal
aging.
This parameter determines the number
of gensets to start, when there is a
REMOTE START signal.
0: Run With Start Power when Remote
0
Start signal arrives
1: Run With Mains Power when Remote
Start signal arrives
2: Run all available gensets when
remote start signal arrives
This parameter decides the number of
gensets to start. If the total power of
100
starting gensets is less than this limit,
then a TOO FEW GENSETS warning
will occur.
0: not used
1: engine shutdown
3
2: load-dump alarm
3: warning
Firmware V-6.3