14.5. TEST MODE

The TEST mode is entered by pressing the
The TEST mode is used in order to test the genset under load.
Once this mode is selected, the engine will run as described in the AUTO mode, regardless of the mains
availability and the load will be transferred to the genset.
The genset will feed the load indefinitely unless another mode is selected.
AMF Mode: The controller will run the engine and make an interrupted transfer.
Synchronizing & Load Sharing Mode: The controller will run the genset. If the busbar is not
energized, it will simply close its genset contactor. If the busbar was energized then it will
synchronize to the busbar, get in parallel, ramp up and start sharing the load.
ATS Mode: The controller will activate its REMOTE START output, thus the genset group will run,
synchronize and close to the busbar. When sufficient power is ready on the busbar, the controller will
transfer the load.
button.
- 84 -