Engine Parameters Group - Datakom D-500 MK2 User Manual

Advanced genset controller
Table of Contents

Advertisement

D-500 MK2 User Manual

17.3. ENGINE PARAMETERS GROUP

Parameter Definition
Nominal RPM
Nominal RPM-2
Nominal RPM-3
Low RPM Warning Limit
Low RPM Shutdown
Limit
High RPM Warning Limit
High RPM Shutdown
Limit
RPM Fail Timer
Overspeed Overshoot
Limit
Loss of Signal Check
Loss of Speed Signal
Action
Loss of Speed Signal
Timer
Low Charge Voltage
Warning Limit
Low Charge Voltage
Shutdown Limit
Unit
Min
Max
rpm
0
50000
rpm
0
50000
rpm
0
50000
%
R-100 R+100
%
R-100 R+100
%
R-100 R+100 R+10%
%
R-100 R+100 R+15%
sec
0
10
HRSL-
HRSL
%
100
+100
-
0
1
-
0
2
sec
0
240
V-DC
0
40
V-DC
0
40
- 111 -
Factory
Set
The nominal value of engine rpm. Low-
1500
high rpm limits are defined by reference
to this value.
When secondary frequency is selected,
this is the nominal value of engine rpm.
1800
Low-high rpm limits are defined by
reference to this value.
When tertiary frequency is selected, this
is the nominal value of engine rpm.
1800
Low-high rpm limits are defined by
reference to this value.
If the engine rpm goes under this limit
R-10%
when feeding the load, this will generate
a GENSET LOW RPM warning.
If the engine rpm goes under this limit
when feeding the load, this will generate
R-15%
a GENSET LOW RPM shutdown alarm
and the engine will stop.
If the engine rpm goes over this limit
when feeding the load, this will generate
a GENSET HIGH RPM warning.
If the engine rpm goes over this limit
when feeding the load, this will generate
a GENSET HIGH RPM shutdown alarm
and the engine will stop.
If the engine rpm goes outside of the
3
limits during this timer, an engine speed
fault will occur.
If the engine rpm goes over the "High
RPM Shutdown Limit" by this quantity,
HRSL
this will generate immediately a GENSET
+10%
HIGH RPM shutdown alarm and the
engine will stop.
0: speed signal existency not checked
1: If the speed signal is lost, it will
0
generate a Speed Signal Lost fault
condition. The action taken upon fault
condition is programmable.
0: shutdown alarm
0
1: loaddump alarm
2: warning
If the speed signal is lost during this
0
timer, a Speed Signal Lost fault will
occur.
If the charge alternator voltage goes
6.0
under this limit, a charge alternator
voltage warning will occur.
If the charge alternator voltage goes
under this limit, a charge alternator
4.0
voltage shutdown will occur and the
engine will stop.
Firmware V-6.3