Sender Configuration - Datakom D-500 MK2 User Manual

Advanced genset controller
Table of Contents

Advertisement

D-500 MK2 User Manual

17.7. SENDER CONFIGURATION

The unit has 4 analog sender inputs. Only parameters of one sender are explained below. Other senders
have identical parameter set.
Each sender has 16 step programmable curves. The sender name and reading unit is freely
programmable, thus the sender can be adapted to any type through programming.
Each sender has below programmable parameters:
Parameter Definition
Sender Type
Alarm Level
Alarm Handling
Sender Open Alarm
Low Alarm Check Enable
Low Warning Check
Enable
High Alarm Check
Enable
High Warning Check
Enable
Low Alarm Level
Low Warning Level
High Alarm Level
High Warning Level
Unit
Min
Max
-
0
15
-
0
1
-
0
3
-
0
3
0
0
1
0
0
1
0
0
1
0
0
1
x
0
10000
x
0
10000
x
0
10000
x
0
10000
- 122 -
Factory
Set
Selects between predefined sender
functions. If this parameter is set to 13-
14-15 then the sender name string can
be freely entered.
0: shutdown alarm
1: loaddump alarm
0: always
1: on engine running
2: after hold-off timer
3: reserved
If sender resistor is above 5000 ohms,
a fault case is generated. This
parameter defines the action taken
upon fault case.
0: no alarm
1: shutdown alarm
2: loaddump alarm
3: warning
The low alarm may be selected as
shutdown or loaddump with "alarm
level" parameter.
0: low value alarm disabled
1: low value alarm enabled
0: low value warning disabled
1: low value warning enabled
The high alarm may be selected as
shutdown or loaddump with "alarm
level" parameter.
0: high value alarm disabled
1: high value alarm enabled
0: high value warning disabled
1: high value warning enabled
If enabled, defines the low alarm limit.
The low alarm may be selected as
shutdown or loaddump with "alarm
level" parameter.
If defined, defines the low warning.
If enabled, defines the high alarm limit.
The high alarm may be selected as
shutdown or loaddump with "alarm
level" parameter.
If defined, defines the high warning.
Firmware V-6.3