765-1505/100-000
Input Arguments
Description of the Output Arguments
Output Arguments
Status and Message
10.3.3.1.10.6 Disabling Forcing
Requirements
• You must have an OPC UA client.
• You must know the username and password, and this user must have permission to
execute methods.
• You must have already established a connection to the I/O module.
• You must have already enabled the Force function and know the Force ID.
Step-by-Step Instructions
1. In the Address Space window, open the context menu: Root > Objects > De-
viceSet > [module name] > Forcing > DisableForcing.
2. In the context menu, select Call.
ð The Call DisableForcing on Forcing window appears.
3. Enter the Force ID.
4. Click [Call].
ð If the method call was successful, then "0" appears under Status, the Force func-
Product manual | Version: 2.0.0
8DIO FLD EI DC 24V 2.0A
tion is disabled, and the FLD LED on the module switches to the off state.
Description
Example 1 (Force Mask has a value of 4): A value of 0
sets the output value of port X03 to 0. A value of 4 sets
the output value of port X03 to 1.
Example 2 (Force Mask has a value of 7): A value of 0
sets the output value of ports X01, X02 and X03 to 0.
A value of 5 sets the output value of port X02 to 0 and
the output value of ports X01 and X03 to 1.
Table 61: Output Arguments of the OutputPin Method
Description
0: Forcing digital outputs successful
−1: Forcing digital outputs failed
Commissioning
99