Diagnostics
CIP Status
25 (0x19)
26 (0x1A)
27 (0x1B)
28 (0x1C)
29 (0x1D)
30 (0x1E)
31 (0x1F)
32 (0x20)
33 (0x21)
34 (0x22)
35 (0x23)
– 36 (0x24)
37 (0x25)
38 (0x26)
39 (0x27)
40 (0x28)
41 (0x29)
42 (0x2A)
106
Product manual | Version: 2.0.0
8DIO FLD EI DC 24V 2.0A
Description
Save attempt failed
The object's attribute data could not be saved because an error occurred during a
save attempt.
Routing error: request packet too large
The routing device had to terminate the service because this service's request
packet was too large for transfer on the network on the path to the destination.
Routing error: response packet too large
The routing device had to terminate the service because this service's response
packet was too large for transfer on the network on the path to the destination.
Missing entry data in attribute list
The service could not supply an attribute of an attribute list which it needs in order
to execute the requested behavior.
Invalid attribute value list
The service returns a attribute list containing the status message "invalid attribute."
An embedded service caused an error
If the embedded service is an IO-Link service: The IO-Link-specific error codes
within the CIP data provide more information of the IO-Link master or IO-Link de-
vice.
Manufacturer-specific error
A manufacturer-specific error occurred. This manufacturer-specific error appears if
none of the general error codes can be used.
Invalid parameter
A parameter in the request is invalid because it does not meet the requirements of
the CIP specification and/or an application object's specification.
Write-once value or medium already written to
An attempt was made to modify the values of a medium although these values
were already written and cannot be written a second time.
Invalid response received
An invalid response was received, for example because a response service code
does not match the request service code, or because the response is shorter than
the expected minimum length.
Reserved
Reserved for future extensions of the CIP standard.
Errors in the key segment
The key segment (the first in the path) does not match the target module. For more
information on which part of the key check failed, see the object status.
Invalid path size
Due to lack of information or an excess of routing data, the path to an object can-
not be routed.
Unexpected attribute in the list
An attempt was made to set an attribute that is not allowed to be set in the current
situation.
Invalid element ID
The member ID in the request is not present in the class/instance attribute.
Element cannot be modified
A request occurred to modify an element that cannot be modified.
General error in the "Only-Group-2 Server"
This DeviceNet-specific error cannot occur in Ethernet/IP.