765-1505/100-000
• ETHERNET Interfaces
– EtherNet/IP
– HTTP for WAGO I/O Field Webserver
– TCP for the OPC UA server
– UDP for WAGO IO-Link Configurator
• Bluetooth
5.6.1 EtherNet/IP
The module exchanges the process data with the controller via EtherNet/IP. The process
data communication requires the controller and module to be configured and parameter-
ized.
Event Log Object 65
IO-Link events are logged in event log object 65 (0x41). The controller or a diagnostic tool
can read event log object 65 (0x41).
5.6.2 OPC UA Server
The module has an integrated OPC UA server.
Function Overview
• Read module identification
• Read configuration
• Read measured values: current, voltage, temperature
• Events: overcurrent, overload and overtemperature
• Read status information
• Read process data
• Read statistics: minimum/maximum current per pin, minimum/maximum voltage per
pin, minimum/maximum temperature
• User access: anonymous (only read access) or username/password (read and write
access)
Product manual | Version: 2.0.0
8DIO FLD EI DC 24V 2.0A
®
for the WAGO I/O Field app
Functions
33