Programming
A flashing cursor will appear in the lower left corner of the display. Type the three digit control module delay in seconds (000 to 180 sec-
ond delay). When the third digit is entered, the display will return to the Delay Screen which will indicate the new delay time. Refer to
the table on page 49 for permissible settings.

NAC (Notification Appliance Circuit)

SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3, or 4 for NAC
4.
The following screens will be displayed for each selection:
NAC #
1=ENABLED
YES
2=TYPE SYNCED STROBE
3=SILENCEABLE
YES
NAC Screen #1
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit
board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
NOTE: The programming for NAC 1 will determine the operation of the remote power supply sync.
Type
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the
display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This will prevent the selected main circuit
board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the
display to toggle between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the
Synced Strobe feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is
enabled. The visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or Autosilence will
turn off both audible and visual devices.
76
The options for the NACs on the control panel main circuit board can be configure by pressing 2 while
viewing System Setup Screen #2. The following screens will be displayed:
1=NAC 1
2=NAC 2
NAC Selection Screen
NAC #
1=AUTO SILENCE
2=CODING
TEMPORAL
NAC Screen #2
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1. The
following screen will be displayed. Press the down arrow key to view additional screens:
1=BELL
2=HORN
3=STROBE
NAC Type Code
Bell
None
Horn
None
Strobe
None
Synced Strobe
Synchronized to manufacturer
Strobe Sil Sync
Same as Synced Strobe but Silence turns off audible & visual devices
Future Use
None
Future Use
None
Future Use
None
Blank
None
NACS
3=NAC 3
4=NAC 4
NAC #
1=ZONE ASSIGNMENT
00
000 000 000 000 000
2=SILENC INHIBIT
NAC Screen #3
NAC TYPE
Type Screen #1
Special Function
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Master Programming Level
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
NO
3=MNS ACTIVE
NAC Screen #4
S
NO
NO