Ann-Bus Options - Honeywell Fire-Lite Alarms ES-200X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-200X:
Table of Contents

Advertisement

Master Programming Level
ANN-RLY Options
ANN XXX
1=ENABLED
YES
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #2
The ANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays Relays 1
through 3. Pressing the down arrow key will display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key corresponding
to the relay to be programmed. Following is a list of the available programming options for each relay:
Alarm
Supervisory
Supervisory AR
Trouble
Comm Fail
Process Mon
Process Mon AR
AC Loss
Hazard
Medical
Silenceable Alarm
Zone Active XXX (where XXX = programmed zone 000 to 099)
Carbon Monoxide
Auto-Configure
XXX ANN-BUS
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
(XXX) ANN-BUS Screen #1
Auto-Configure process and cause the following screen to be displayed:
Class A
XXX ANN-BUS
1=CLASS A
ANN-BUS (XXX) Screen #2

ANN-BUS Options

ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciator Screen
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Pressing 2 for Module Options while viewing the ANN-BUS Address Screen when the ANN-RLY option is
selected, will cause the following screen to be displayed:
ANN-RLY - ADDR. X-1
1=RLY 1
2=RLY 2
3=RLY 3
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS
YES
modules online on the selected ANN-BUS. The software will search the selected circuit for all ANN-BUS
modules and automatically program the device type and address into the system. For the Auto-Configure to
work, the selected ANN-BUS must be enabled, the annunciators must be connected/powered, and a unique
address must be set on each annunciator. Pressing 3 while viewing ANN-BUS (X) Screen #1 will begin the
This option applies to the Primary ANN-BUS only. The primary ANN-BUS can be configured for Class A
NO
wiring. If wired in Class A configuration, press 1 on ANN-BUS Primary Screen #2 to select Class A Yes.
Each press of the 1 key toggles between Class A No and Class A Yes.
Three ANN-BUS modules have more programming options. Pressing 3 while viewing the Annunciators
screen will display the following.
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ZONE 000
ZONE 001
ZONE 002
ANN-RLY Options Screen
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
ANN-BUS
ANN-BUS Options Screen
Programming
97