Optional Module Installation
4XTMF
NOTE: When a 4XTMF is installed, enable supervision in panel programming.
Jumper JS3 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module.
Relay 3 at TB3 must be programmed as a supervisory relay.
Jumpering pins 2&3 on JS3 will allow the 4XTMF to generate a trouble if the supervisory contact opens.
Jumpering pins 1&2 on JS3 in will prevent generation of a trouble if the supervisory contact opens.
2.8.4 ANN-BUS Annunciators/Modules

ANN-BUS Wiring

This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B).
Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used
with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case
current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst
case currents for each module. The individual worst case values are shown in the following table:
1
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Standoff
J12 & J13 Connectors
Figure 2.16 4XTMF Connectors to ES-200X Connectors
Model Number
ANN-80 LCD Annunciator
ANN-100 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-(R)LED Annunciator Module
ANN-RLY Relay Module
When powering the ANN-BUS from one of the (nonresettable) DC power outputs at TB11, the
total worst case current draw cannot exceed 1.0 amp. If sharing this DC output with other devices,
the worst case current drawn by these devices must be combined with the ANN-BUS current draw,
and the total cannot exceed 1.0 amp. If the total current demand exceeds 1.0 amp, refer to
"Powering ANN-BUS Devices from an Auxiliary Power Supply" on page 35.
ALRM
NO
NC
C
Jumper JS3
Standoff
FACP main circuit board
0.040 amps
0.025 amps
0.040 amps
0.200 amps
0.068 amps
0.075 amps
TRBL
SUPV
RMT SYNC
NAC1
NO
NC
C
OUT+
RTN+
RTN- OUT-
NO
NC
C
1
2
3
1
Worst Case Current Draw
Installation
33