Master Programming Level
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices pro-
grammed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine
seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be programmed for either PAS or Pre-
signal operation. Refer to"Edit Detector" on page 54 for programming details.
Waterflow Delay
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-
five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the
Delay Screen which will indicate the new delay time.
AC Loss Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
Timer Screen #2
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central sta-
tion.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour
delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1. Refer to the table on page 49 for permissi-
ble settings.
NOTE: Upon the loss of AC power at the control panel, relays programmed for 'AC Loss' will transfer immediately, regardless of the AC
Loss Delay setting. If no trouble exists at the panel other than AC Loss, the System Trouble relay will delay its activation for the duration of
the AC Loss Delay setting.
Control Module Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
Timer Screen #2
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
PRESIGNAL DELAY
RANGE 0-180 SECONDS

Pre-signal Delay Screen
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays
of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a
Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing
Timer Screen #1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS

Waterflow Delay Screen
The reporting of a loss of AC power to a central station can be delayed by programming the length of the
desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2 to display the
following:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
AC LOSS DELAY
RANGE 00-23

AC Loss Delay Screen #2
The control module delay feature, if enabled, will delay activation of a control module after being triggered
by an alarm condition. Pressing 2 while viewing Timer Screen #2 will display the following:
CTRL MOD DELAY
RANGE 0-180 SECONDS

Control Module Delay Screen
Programming