NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Cut Jumper JP3 on the ES-200X main circuit board to supervise placement of the 4XTMF module.
2.
Refer to "4XTMF Transmitter Module Installation" on page 31 for detailed information.
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
140
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
Figure C.2 Remote Station Connection Using 4XTMF Module
Polarity Shown is
+
-
Normal Standby
+
Power-limited
-
(Dummy load with a 4.7K
when no connection is made)
4XTMF Transmitter Module
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Ω
, ¼ watt resistor