Appendix F: Ademco Contact Id Format Event Code Descriptions; F.1: Transmission Format Between Dact And Receiver; F.2: Ademco Contact Id Typical Printout - Honeywell Fire-Lite Alarms ES-200X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-200X:
Table of Contents

Advertisement

Appendix F: Ademco Contact ID Format Event Code Descriptions

This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format.
F.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
SSSS
Four digit Subscriber ID Account Code
18=
Identifies transmission as Contact ID to the receiver at the Central Station
Q=
Event Qualifier where 1 = New Event and 3 = New Restore
XYZ=
Event code
GG=
Group number
CCC=
Zone/Point number
Notes:
1.
18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the alarm and trouble
report.
2.
GG Group Number is fixed at '00'.
3.
CCC for Zone or Point Number:
 Zone Number is transmitted as '01' for zone 1 up to '99' for zone 99
 Point Number is transmitted as '01' for point/address 1 up to '99' for point/address 99
F.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID
Reporting Structure follows:
Time
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
Notes:
1.
11 is an example of a Receiver/Line Card, showing which receiver and line card the message was transmitted to.
2.
Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or R for New Restore.
147
where
Date
Rcvr/Line ID
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
SSSS
QXYZ
GG
7777
E110
00
7777
E111
00
7777
E380
00
7777
E570
00
7777
R110
00
7777
R111
00
7777
R380
00
7777
R570
00
7777
E158
00
7777
E151
00
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
CCCC
C001 - general fire alarm on zone one
C002 - smoke detector alarm on zone two
C003 - fault on zone three
C009 - Zone nine disabled
C001 - Zone one alarm restored
C002 - smoke detector zone two restored
C003 - zone three fault restored
C009 - zone nine reenabled
C006 - high temperature, zone six
C007 - gas detected, zone seven

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-200xc

Table of Contents