Programming
Type Monitor
EDIT MONITOR
1=ENABLED
2=TYPE MONITOR
Edit Monitor Screen #2
Pressing the down arrow key will display additional Monitor Type screens. While viewing one of the Monitor Type screens, select the
type of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Moni-
tor Screen #2 which will show the new type selection.
Table 3.1 lists the Monitor Types and their respective functions.
Monitor module type selection will affect the function of the point as follows:
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Future
Future
Smoke-Conventional
User-Defined-5
Heat Conventional
User-Defined-6
Medic Alert
User-Defined-7
Hazard Alert
User-Defined-8
Tornado Alert
User-Defined-9
Phone
User-Defined-10
Tamper
User-Defined-11
Supervisory
User-Defined-12
Supervisory AR
User-Defined-13
HVAC OVRRIDE
Power Monitor
User-Defined-14
Trouble Monitor
User-Defined-15
Process Monitor
User-Defined 16
Process-Monitor-AR
User-Defined-17
MNS Event
User-Defined-18
62
Using the FS-Tools Upload/Download utility, unique user-defined monitor types can be created and loaded
into the FACP for later use. The FACP response to the activation of a user-defined type is the same as most
previous standard types in the list, thus allowing a variety of user-defined types and responses. To select the
type of monitor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2. This
will cause the control panel to display the following Monitor Type Screens:
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1
Monitor Type
Fire Alarm
same as previous (Pull-Station)
Fire Alarm Delayed
same as previous (Waterflow)
Fire Alarm
same as previous (Monitor)
not used
not used
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
1
General Purpose Signaling, latching
same as previous (Medic-Alert)
1
General Purpose Signaling, latching
same as previous (Hazard-Alert)
1
General Purpose Signaling, latching
same as previous (Tornado-Alert)
Active Phone (LCD display only)
same as previous (Phone)
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
same as previous (Supervisory)
2
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
3
Switch Supervisory, nonlatching (tracking)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
General Purpose Signaling, latching
1
same as previous (Process-Monitor)
1,2
General Purpose Signaling, nonlatching (tracking)
same as previous (Process-Monitor-AR)
Allows the Mass Notification System to override FACP programming and
turn off designated active outputs
same as previous (MNS Event)
Action When Activated
Table 3.1 Monitor Types
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Master Programming Level